Hankwang Electric Industrial Power Equipment
South Korean switchgear (7.2–24 kV, E-GIS, MCSG), HMC8000 motor control centers, HK-N/TN ATS, ATB-EX/ATBC transfer breakers, BPIS/CTTS bypass systems, and VTB vacuum units.
High-Tension Switchgear, E-GIS & MCSG
Switchboards for 7.2, 15, and 24 kV feature a 3-level compartmentalized layout (2350×1800 mm) for substations. The line covers KERI-tested MCSG, eco-friendly E-GIS, and SIS units with optical arc sensors. Spares cover VCBs, LBS, 200 A fuses, arresters, CTs, and PT trucks.
- Voltage ratings: 7.2 / 15 / 24 kV
- Series: MCSG, E-GIS, SIS, F2/G
- Optical arc & PD detection
- Parts: VCB, LBS, CT/PT, arresters
HMC8000 Motor Control Centers (MCC)
HMC8000 motor control centers use drawer units up to 800 A in 1/4, 1/2, 1, and 2–3 module sizes. Front 1–3 step withdrawal isolates circuits while keeping enclosure IP protection under live bus. Permanent-magnet contactors (PM MC) cut holding power by 95% without coil heating.
- Series: HMC8000 up to 800 A
- Drawers: 1/4, 1/2, 1, 2–3 modules
- PM MC contactors (-95% standby)
- Parts: drawers, PM MC, interlocks
Automatic Transfer Switches ATS HK-N / HK-TN
ATS N-type (HK-63N–250N) and TN-type (HK-125TN–3200TN) units operate at AC 600 V / DC 125 V in 2P/3P/4P. Short-time withstand Icw reaches 5 kA on N-type and 50 kA on HK-3000/3200TN with 5,000 electrical cycles. Spares cover A/B close coils, AUX contacts, and control relays.
- HK-N: 63–250 A | HK-TN: 100–3200 A
- Rated Ue: AC 600 V / DC 125 V
- Short-time Icw: 5 to 50 kA
- Parts: A/B coils, AUX, control units
Automatic Transfer Breakers ATB-EX & ATBC
ATB breakers combine two ACBs per IEC 60947-6-1 (Ui 1000 V, Ue 690 V AC) with overlapping neutral. ATB-EX covers 630–6000 A (Icw 50–100 kA at 460 V), while compact ATBC spans 400–1600 A (32 kA). Spares include 24 VDC–220 VAC motor chargers, coils, and OCR/GR relays.
- ATB-EX: 630–6000 A (50–100 kA)
- ATBC: 400–1600 A (32 kA / 67.2 kA)
- Fixed & draw-out (4-position rail)
- Parts: motor charger, OCR/GR, coils
BPIS Bypass Isolation, CTTS & HANpro3000
MV BPIS panels (7.2, 12, and 24 kV; 630–1600 A; 25–31.5 kA) isolate the main VTB on bypass without dropping load. Closed-transition CTTS units perform make-before-break transfers (>100 ms) via the HANpro3000 controller. Spares cover HANpro3000 units, interlocks, and bypass drives.
- MV BPIS: 7.2 / 12 / 24 kV, 630–1600 A
- Withstand: 31.5 kA (12 kV) / 25 kA (24 kV)
- CTTS closed-transition (>100 ms)
- HANpro3000 controller & mimic panel
Double Vacuum Transfer Breakers (VTB)
VTB units (7.2–12 kV and 24 kV) meet IEC 60947-6-1, IEC 62271-100, ANSI C37, and GB/T 1984-2003. Electric motor charging and a dual-OFF neutral position suit draw-out, fixed, and bypass cubicles. Spares include contact arms, plum-blossom contacts, pole posts, and chassis.
- Ratings: 7.2–12 kV & 24 kV
- IEC 62271-100 & IEC 60947-6-1
- Draw-out, fixed & built-in bypass
- Parts: contact arms, plum contacts, poles
Duplex Distribution Boards & Bus Duct
HKE Duplex boards feature a flame-retardant busbar module with vertical busbars and ELB safety covers, cutting footprint up to 30%. The range also covers KS Bus Duct lines and patented busbar joint kits. Service spares include insulated busbar blocks and ELB protective covers.
- Up to 30% smaller board footprint
- Flame-retardant insulated busbar module
- Bus Duct systems & joint kits
- Parts: busbar blocks, ELB safety covers
Industrial Switchgear, MCC, and Transfer Switch Portfolio
Founded in 1960 in South Korea, Hankwang Electric Ind. Co., Ltd. (HKE) manufactures low- and medium-voltage power equipment up to 24 kV, including 3-level high-tension switchboards (7.2 / 15 / 24 kV), KERI-tested arc-resistant MCSG, eco-friendly E-GIS, and KS-compliant Bus Duct systems.
For industrial plants, data centers, and power utilities, the lineup includes HMC8000 draw-out motor control centers (up to 800 A) with permanent-magnet contactors, HK-N/TN ATS (63–3200 A), ATB-EX (630–6000 A) and ATBC (400–1600 A) transfer breakers, MV BPIS/CTTS bypass systems with HANpro3000 controllers, and 7.2–24 kV VTB units.
Engineering Selection & Homonym Clarification
Equipment selection relies on system voltage class (600 V / 690 V / 7.2–24 kV), rated current (63–6000 A), short-time withstand current (5–100 kA), pole configuration (2P/3P/4P with overlapping neutral option), fixed or draw-out cassette structure, and IEC 60947-6-1 / IEC 62271-100 compliance.
Hankwang Electric (hkelec.co.kr) strictly denotes the South Korean switchgear and power apparatus manufacturer and should not be confused with Hankwang / HK Laser metal-cutting machinery or Hankwang Opto optical lens producers.
Hankwang Electric and model names are trademarks of their respective owners and are used only to identify the equipment for which we source parts. SpareX is not an official dealer, distributor or representative of Hankwang Electric and is not affiliated with the trademark owner. Origin, documents and warranty are stated for each item in the quotation.
Related equipment manufacturers
- Equipment and parts for Broadcom / Avago Technologies
- Equipment and parts for E.MC Pneumatics / Zhejiang Eternal Automation
- Equipment and parts for HAM-LET Group
- Equipment and parts for Hangzhou Shanli Purify
Documents and sources
- Hankwang Electric — official English product portal (Switchgear, MCC, ATS, ATB, BPIS & CTTS, VTB, Duplex)
- Hankwang Electric — company overview, founding date (1960/1974), and plant details
- Hankwang Electric — R&D milestones, KERI tests (MCSG, E-GIS), HMC-8000, and Bus Duct
- Hankwang Electric — patents (VTB, optical arc/PD sensors, busbar joint kit) and trademarks
- Hankwang Electric — industrial and power station reference projects
- Hankwang Electric — power equipment division (Switchgear, E-GIS, MCSG, Bus Duct)
- Hankwang Electric — breaker & transfer division (ATS, ATB, BPIS/CTTS, VTB, HANpro, EMCC)
- Hankwang Electric — next-generation optical fiber sensors and wireless thermal monitoring
- Hankwang Electric — customer support and repair/after-sales request portal
- Hankwang Electric — High Tension Switchboard specification (7.2 / 15 / 24 kV)
- Hankwang Electric — HMC8000 Motor Control Center & PM Magnetic Contactor specification
- Hankwang Electric — ATS Automatic Transfer Switches N-Type & TN-Type specification
- Hankwang Electric — ATB-EX & ATBC Compact Automatic Transfer Breaker specification
- Hankwang Electric — BPIS Medium-Voltage Transfer & CTTS / HANpro3000 specification
- Hankwang Electric — VTB Double Vacuum Circuit Breaker specification (7.2–12 kV & 24 kV)
- Hankwang Electric — Duplex Distribution Board technical overview