Franklin Fueling Systems tank gauges
Technical selection of Franklin Fueling Systems tank gauges: EVO 600, EVO 6000 and EVO ONE consoles, TS-550 and TS-5000 modules, FMP-LL3 digital probes, TSP-LL2 analog probes, density floats and sump sensors.
EVO 600 and EVO 6000 tank gauge consoles
The module-based EVO 600 and EVO 6000 consoles handle fuel inventory, tank testing and containment monitoring. Stand-alone, each monitors up to 48 tanks, and EVO 600 accepts up to 80 sensors. Interfaces are Ethernet, RS-232 and RS-485 with MQTT, Modbus and XML.
- Up to 48 tanks stand-alone
- EVO 600: up to 80 sensors
- Up to 34 relay outputs
- Power 110–240 VAC, 50/60 Hz
Compact EVO ONE and EVO 400 consoles
Compact EVO ONE and EVO 400 consoles suit fuel sites with up to 14 tanks. EVO ONE has 14 Universal Device Protocol inputs, 4 line channels, 4 relay outputs and 2 dry contact inputs. FMP-LL3 probes are ordered with EVO ONE kits as a separate line item.
- Up to 14 tanks
- Line capacity: 4 lines
- Power 110–240 VAC, 1.0 A
- EVO 400 housing 350 × 83 × 205 mm
TS-550 and TS-5000 console modules
TS-550, TS-5000 and EVO 550/5000 consoles take replacement modules: the EVO-CM/R controller programmed with required options, the TSSP-PS power supply, the TSSP-PRB probe module and the intrinsically safe TSSP-420IB 4–20 mA module. EVO-600UPG upgrades EVO 550 to EVO 600.
- EVO-CM/R controller module
- TSSP-PRB probe module
- TSSP-420IB 4–20 mA module
- EVO-EXPC adds 11 modules
FMP-LL3 digital level probes
FMP-LL3 magnetostrictive probes measure product and water levels and carry 5 thermistors in the shaft, with ±0.2 mm product level accuracy. The probe sends its gradient, type, length and serial number to the console. FMP-LL3-89, FMP-LL3-101 and FMP-LL3-113 are 7, 8 and 9 ft long.
- Product accuracy ±0.2 mm
- 5 thermistors in the shaft
- FMP-LL3-113 probe: 9 ft
- Operating −40 to +60 °C
TSP-LL2 analog level probes
TSP-LL2 analog probes work with TS-5, TS-550, TS-5000 and EVO Series gauges and carry up to three floats for product, water, phase separation or density. Non-linearity is ±0.025% of full scale with a 10 ft shielded cable. TSP-LL2-101 is a 101-inch leak detection probe.
- Non-linearity ±0.025% FS
- Up to three floats per probe
- Probe cable: 10 ft
- TSP-LL2-101 probe: 101 in
Flexible probes for tall tanks
Flexible probes cover tanks from 1,219 to 20,726 mm, including aboveground tanks and low-clearance indoor rooms. The probe is uncoiled at the riser and fed into the tank; a 406 mm stainless steel guide sleeve and a bottom weight keep it vertical. Tanks up to 22,200,000 L are supported.
- Length 1,219–20,726 mm
- Tanks up to 22,200,000 L
- 406 mm stainless guide sleeve
- Probe weight and pin included
Density, water and phase separation floats
TSP-IGF4D3 gasoline and TSP-IDF4D3 diesel kits measure density with ±3.0 kg/m3 accuracy; the probe serial number must be above 6000000. TSP-IGF4P detects phase separation in gasoline up to E15, and FMP-IDF4E detects low-level water in diesel tanks.
- TSP-IGF4D3 gasoline density kit
- TSP-IDF4D3 diesel density kit
- Density accuracy ±3.0 kg/m3
- TSP-IGF4P phase separation, E15
Sump sensors and line leak detection
The FMP-DDS sensor tells fuel from water in dispenser sumps and alarms on liquid 38 mm above its base. FMP-HIS monitors brine in double-wall tank interstices. EVO LLD tests pressurized lines after every dispense cycle and works with submersible pumps from 1.7 bar.
- FMP-DDS: liquid at 38 mm
- FMP-HIS interstitial sensor
- Line test 11 L/h
- Pumps from 1.7 bar
Choosing a Franklin Fueling Systems console by tank count
The EVO Series includes compact EVO ONE and EVO 400 consoles for fuel sites with up to 14 tanks and module-based EVO 600 and EVO 6000 consoles that monitor up to 48 tanks stand-alone. EVO 600 accepts up to 80 sensors, with up to 34 relay outputs.
Installed TS-550, TS-5000 and EVO 550/5000 consoles are served by replacement modules and upgrade kits: the EVO-CM/R controller, the TSSP-PRB probe module and the EVO-600UPG kit that moves EVO 550 to EVO 600.
Probes and floats for the tank and fuel
FMP-LL3 digital magnetostrictive probes give ±0.2 mm product level accuracy and report their type, length and serial number to the console. TSP-LL2 analog probes work with TS-5, TS-550 and TS-5000 consoles. Flexible probes from 1,219 to 20,726 mm serve tall aboveground tanks.
Floats are chosen by fuel and task: standard product and water kits, TSP-IGF4D3 and TSP-IDF4D3 density kits with ±3.0 kg/m3 accuracy, and the TSP-IGF4P phase separation float for gasoline up to E15.
Sump and line monitoring, data links
The FMP-DDS sensor tells fuel from water in dispenser sumps, and FMP-HIS monitors the interstitial space of double-wall tanks. EVO LLD tests pressurized lines after every dispense cycle and works with submersible pumps from 1.7 bar.
EVO 600 and EVO 6000 consoles connect over Ethernet, RS-232 and RS-485 and support MQTT, Modbus and XML protocols for site data systems.
Franklin Fueling Systems and model names are trademarks of their respective owners and are used only to identify the equipment for which we source parts. SpareX is not an official dealer, distributor or representative of Franklin Fueling Systems and is not affiliated with the trademark owner. Origin, documents and warranty are stated for each item in the quotation.
Related equipment manufacturers
- Equipment and parts for Fast Fueling
- Equipment and parts for APG / Automation Products Group
- Equipment and parts for DINEL
- Equipment and parts for Endress+Hauser
Documents and sources
- Franklin Fueling Systems — facilities
- Franklin Electric — company history
- EVO 600 and EVO 6000 — specifications
- EVO ONE — specifications
- EVO 200 and EVO 400 — specifications
- Legacy replacement parts — TS-550 and TS-5000 modules
- FMP-LL3 digital probes — specifications
- TSP-LL2 analog probes — specifications
- Flexible inventory probes — specifications
- Density float kits — specifications
- Phase separation float kits — specifications
- Low level water float for diesel — description
- Standard float kits — description
- FMP-DDS dispenser sump sensor — specifications
- FMP-HIS hydrostatic interstitial sensor — specifications
- EVO LLD line leak detection — specifications