Franklin Fueling Systems tank gauges

Technical selection of Franklin Fueling Systems tank gauges: EVO 600, EVO 6000 and EVO ONE consoles, TS-550 and TS-5000 modules, FMP-LL3 digital probes, TSP-LL2 analog probes, density floats and sump sensors.

EVO 600 and EVO 6000 tank gauge consoles

The module-based EVO 600 and EVO 6000 consoles handle fuel inventory, tank testing and containment monitoring. Stand-alone, each monitors up to 48 tanks, and EVO 600 accepts up to 80 sensors. Interfaces are Ethernet, RS-232 and RS-485 with MQTT, Modbus and XML.

  • Up to 48 tanks stand-alone
  • EVO 600: up to 80 sensors
  • Up to 34 relay outputs
  • Power 110–240 VAC, 50/60 Hz

Compact EVO ONE and EVO 400 consoles

Compact EVO ONE and EVO 400 consoles suit fuel sites with up to 14 tanks. EVO ONE has 14 Universal Device Protocol inputs, 4 line channels, 4 relay outputs and 2 dry contact inputs. FMP-LL3 probes are ordered with EVO ONE kits as a separate line item.

  • Up to 14 tanks
  • Line capacity: 4 lines
  • Power 110–240 VAC, 1.0 A
  • EVO 400 housing 350 × 83 × 205 mm

TS-550 and TS-5000 console modules

TS-550, TS-5000 and EVO 550/5000 consoles take replacement modules: the EVO-CM/R controller programmed with required options, the TSSP-PS power supply, the TSSP-PRB probe module and the intrinsically safe TSSP-420IB 4–20 mA module. EVO-600UPG upgrades EVO 550 to EVO 600.

  • EVO-CM/R controller module
  • TSSP-PRB probe module
  • TSSP-420IB 4–20 mA module
  • EVO-EXPC adds 11 modules

FMP-LL3 digital level probes

FMP-LL3 magnetostrictive probes measure product and water levels and carry 5 thermistors in the shaft, with ±0.2 mm product level accuracy. The probe sends its gradient, type, length and serial number to the console. FMP-LL3-89, FMP-LL3-101 and FMP-LL3-113 are 7, 8 and 9 ft long.

  • Product accuracy ±0.2 mm
  • 5 thermistors in the shaft
  • FMP-LL3-113 probe: 9 ft
  • Operating −40 to +60 °C

TSP-LL2 analog level probes

TSP-LL2 analog probes work with TS-5, TS-550, TS-5000 and EVO Series gauges and carry up to three floats for product, water, phase separation or density. Non-linearity is ±0.025% of full scale with a 10 ft shielded cable. TSP-LL2-101 is a 101-inch leak detection probe.

  • Non-linearity ±0.025% FS
  • Up to three floats per probe
  • Probe cable: 10 ft
  • TSP-LL2-101 probe: 101 in

Flexible probes for tall tanks

Flexible probes cover tanks from 1,219 to 20,726 mm, including aboveground tanks and low-clearance indoor rooms. The probe is uncoiled at the riser and fed into the tank; a 406 mm stainless steel guide sleeve and a bottom weight keep it vertical. Tanks up to 22,200,000 L are supported.

  • Length 1,219–20,726 mm
  • Tanks up to 22,200,000 L
  • 406 mm stainless guide sleeve
  • Probe weight and pin included

Density, water and phase separation floats

TSP-IGF4D3 gasoline and TSP-IDF4D3 diesel kits measure density with ±3.0 kg/m3 accuracy; the probe serial number must be above 6000000. TSP-IGF4P detects phase separation in gasoline up to E15, and FMP-IDF4E detects low-level water in diesel tanks.

  • TSP-IGF4D3 gasoline density kit
  • TSP-IDF4D3 diesel density kit
  • Density accuracy ±3.0 kg/m3
  • TSP-IGF4P phase separation, E15

Sump sensors and line leak detection

The FMP-DDS sensor tells fuel from water in dispenser sumps and alarms on liquid 38 mm above its base. FMP-HIS monitors brine in double-wall tank interstices. EVO LLD tests pressurized lines after every dispense cycle and works with submersible pumps from 1.7 bar.

  • FMP-DDS: liquid at 38 mm
  • FMP-HIS interstitial sensor
  • Line test 11 L/h
  • Pumps from 1.7 bar

Choosing a Franklin Fueling Systems console by tank count

The EVO Series includes compact EVO ONE and EVO 400 consoles for fuel sites with up to 14 tanks and module-based EVO 600 and EVO 6000 consoles that monitor up to 48 tanks stand-alone. EVO 600 accepts up to 80 sensors, with up to 34 relay outputs.

Installed TS-550, TS-5000 and EVO 550/5000 consoles are served by replacement modules and upgrade kits: the EVO-CM/R controller, the TSSP-PRB probe module and the EVO-600UPG kit that moves EVO 550 to EVO 600.

Probes and floats for the tank and fuel

FMP-LL3 digital magnetostrictive probes give ±0.2 mm product level accuracy and report their type, length and serial number to the console. TSP-LL2 analog probes work with TS-5, TS-550 and TS-5000 consoles. Flexible probes from 1,219 to 20,726 mm serve tall aboveground tanks.

Floats are chosen by fuel and task: standard product and water kits, TSP-IGF4D3 and TSP-IDF4D3 density kits with ±3.0 kg/m3 accuracy, and the TSP-IGF4P phase separation float for gasoline up to E15.

Sump and line monitoring, data links

The FMP-DDS sensor tells fuel from water in dispenser sumps, and FMP-HIS monitors the interstitial space of double-wall tanks. EVO LLD tests pressurized lines after every dispense cycle and works with submersible pumps from 1.7 bar.

EVO 600 and EVO 6000 consoles connect over Ethernet, RS-232 and RS-485 and support MQTT, Modbus and XML protocols for site data systems.

Industrial equipment

Request a quote

Describe your requirements and attach up to 5 files, each up to 20 MB.

You can also drag photos or documents here.

You can also email us. Opening your email app does not send an enquiry automatically.

WeChat · Nastia

English-speaking contact

WeChat QR code: Nastia

Scan the QR code to add Nastia on WeChat.

Save QR image

On this phone: save the image, then choose it from your photos in WeChat’s scanner.

Telegram · Nastia

Contact Nastia

Telegram QR code: @ananasprosto

Scan the QR code or open @ananasprosto in Telegram.@ananasprosto в Telegram.

Save QR image

Scan the QR code or open @ananasprosto in Telegram.