Macromatic phase monitor, current sensing and time delay relays

Technical selection of Macromatic Industrial Controls relays (Waukesha, Wisconsin, USA): three-phase, voltage and current monitor relays, time delay relays, pump alternating relays, level and seal leak relays, intrinsically safe barrier relays.

PMP, PMD, PxE and PC1 three-phase monitors

Depending on model, they protect three-phase equipment against phase loss, reversal, unbalance, undervoltage and overvoltage; no neutral connection is required. PMP plugs into an 8 pin octal socket, PxE and PBDU are 17.5 mm and PMD 52.5 mm wide on 35 mm DIN rail. PC1 reports status over Modbus TCP.

  • PMPU: unbalance 2-10%
  • PBDU: unbalance 5-25% or off
  • PMD enclosure: 52.5 mm
  • PC1MDUL: Modbus TCP, 60 mm

VMP, VWKP and VxE voltage monitor relays

They monitor AC single phase or DC voltage and are powered by the monitored voltage itself. VMP and VAKP provide over/under voltage protection, VWKP keeps the load within an upper and lower voltage band, and the narrow VxE series mounts on 35 mm DIN rail.

  • VMP480A: drop-out at 95% of pick-up
  • VMP480A delay: 0.5 s
  • VMP480A sensing accuracy ±2%
  • Powered by monitored voltage

CMD, CAH, COH and CUH current sensing relays

They detect locked rotor or load loss, conveyor jam-ups, machine tool wear, heater or lamp loads. The multifunction CMD series monitors AC and DC current in overcurrent, undercurrent and band (window) modes with a latch option, while encapsulated CAH, COH and CUH units serve harsh environments.

  • CMD10AD2U: 5 mA to 10 A
  • CMD10AD2U trip delay 0.1-10 s
  • CMD enclosure: 22.5 mm
  • CMD hysteresis 5-95% of pick-up

TR-6, TD-8 and TH4 time delay relays

They come in four mounting configurations: plug-in, encapsulated, DIN rail and door mounted. TR-6022U covers 0.05 seconds to 100 hours in 16 ranges on 24-240V AC and 12-125V DC, TD-8 is programmed with DIP switches, and TH4 switches 30 A loads without a separate contactor.

  • TR-6022U: 0.05 s to 100 h
  • TR-6022U: 16 timing ranges
  • TD-80221-40: 0.1-102.3 s
  • TH4 series: 30 A loads

ARP, ARF and ATP alternating relays

They equalize run time of redundant pumps and other loads: each time the float or pressure switch opens, the relay changes state. ARP controls two loads, ARP Duplex runs S.O.S.O. operation with three float switch inputs, ARF mounts on the inner door, ATP controls three loads.

  • ATP120A1: LEAD, LAG, LAG2 inputs
  • ATP120A1: 10 s delay after power return
  • ARP Duplex: three float inputs
  • ARF: inner-door mounting

LCP liquid level control relays

LCP relays regulate levels of conductive liquids in pump up (fill) or pump down (drain) duty: water, sewage and solutions. The probe is pulsed with DC voltage to prevent electroplating. Single probe models have ten factory delays from 1 to 60 seconds, dual probe models match competitive pin layouts.

  • LCP8C100: 4.7-100 kOhm range
  • Probe voltage: 5V DC pulsed
  • Single probe: 1-60 s delay
  • Pin layouts match other makes

SFP, TCP and TCF seal leak and temperature relays

They watch shaft seals of submersible pumps: when fluid leaks into the seal cavity, resistance between probe and motor housing drops below the set-point and the output alarms. SFP has one or two channels, TCP and TCF also sense overheating; TCF-E suits float-type sensors, TCF-F CLS or FLS sensors.

  • SFP240C100: two pumps
  • SFP240C100: 4.7-100 kOhm
  • TCF8D100 over temperature: 5 kOhm
  • TCF8D100: auto and manual reset

ISD, ISE and ISP intrinsically safe barrier relays

They keep excess voltage and current out of the hazardous area and control loads without extra relays or contactors. Approved for Class I, II and III, Div 1. ISD controls up to four loads (ISDUM4 is set per channel), ISE a single load; ISP is not approved for hazardous zones in Canada.

  • ISD: up to four channels
  • ISDUM4: 0 or 2 s delay
  • ISDUM4 input: 10V DC open circuit
  • Class I, Div 1 locations

Choosing phase, voltage and current monitor relays

Macromatic relays are used in water/wastewater, pump and motor control, irrigation, oil and gas, HVACR, material handling, lifts and elevators.

For three-phase systems the phase monitor is chosen by enclosure: PMP plugs into an 8 pin octal socket, PxE and PBDU are 17.5 mm wide, PMD is 52.5 mm wide, PC1 is 60 mm wide with Modbus TCP.

AC single phase and DC voltage is monitored by VMP and VAKP (over/under) or VWKP (band); they are powered by the monitored voltage. CMD10AD2U monitors load current from 5 mA to 10 A in overcurrent, undercurrent and band modes.

Time delay relays: range and setting method

TR-6022U is analog set with 16 built-in timing ranges from 0.05 seconds to 100 hours and a universal 24-240V AC and 12-125V DC input. TD-80221-40 is set by DIP switches over 0.1-102.3 seconds. Encapsulated TH4 relays switch 30 A loads without a separate contactor.

Where timing must be started by voltage rather than a dry contact, choose the power trigger versions of the TR-5 and TR-6 series.

Pump stations: alternation, level, seal leakage

ARP alternating relays suit two pumps, ATP120A1 suits three, with LEAD, LAG and LAG2 inputs and a fixed 10 second delay between starts after power returns. LCP relays hold the level of conductive liquids in fill or drain duty; LCP8C100 has a 4.7-100 kOhm sensitivity range.

Submersible pumps are protected by SFP seal leak relays (SFP240C100 watches two pumps) and combined TCF relays (TCF8D100 has a 5 kOhm over temperature setting). In hazardous areas, field switches connect through four-channel ISD or single-channel ISE barrier relays.

Industrial equipment

Request a quote

Describe your requirements and attach up to 5 files, each up to 20 MB.

You can also drag photos or documents here.

You can also email us. Opening your email app does not send an enquiry automatically.

WeChat · Nastia

English-speaking contact

WeChat QR code: Nastia

Scan the QR code to add Nastia on WeChat.